Mounting
One hinge bracket and one fix angle bracket.
The hinge makes it possible to move the fixture to free position for removing the gear tray when maintaining the fixture.
Optic
Diffuser in impact-proof UV-resistant polycarbonate
Electric
With magnetic ballasts and capacitor (F) or electronic ballast (HF). Emergency versions with integral battery available on request. AC 115, 220, 230 V ± 10% 50<60 Hz.
Housing
Robust housing in poycarbonate tube with seawater resistant end caps. End caps are designed for glue connection to both sides of polycarbonate tube.
Lightsource/Optic
Two tubes T26 (T8), 18 or 36 W. Variants with light sources mounted available on request. Lamp base G13.
Application
For mounting indoor and outdoor in Zone 1 areas.
Designed according to IEC, EX and maritime requirements. ATEX and IECEx approved.
Finish
End caps powder coated withe RAL9016
Connection
One Ex d cable gland on one side, and one blind plug on the other side of the same end cap (M20 or M25). Also one gland each side of one end cap available on request. One 3-way crew terminal block 6 mm² with quick connector on gear tray.